Manual #5403546-E10/09POTTER ELECTRIC SIGNAL COMPANY, LLCSt. Louis, MO (866) 956-1211 • (314) 595-6900 • FAX (314) 595-6999www.pottersignal.comPFC-500
6Figure 2: PFC-5004E/PFC-5008 Enclosure Installation and DimensionsFINISH: PAINTEDDOOR 16GA (0.059") THICKCOLD ROLLED STEELDOORBACKBOX(SIDE VIEW)
7Modules Mounting LocationsThe PFC-5000 Series come pre-assembled with all components and boards, except for adder modules. Module installation locati
8Fig. 4: PFC-5004E/PFC-5008 Module Mounting LocationsP8P7DISPLAYPLATEZONE ADDERMODULE(ZA-42)MAIN FIREALARMMODULEP1P6(MODEL PR-5100)POLARITY REVERSAL A
9Module SettingsMain Fire Alarm ModuleClass A / B SelectionOn the PFC-5002, PFC-5004, PFC-5008 and PFC-5004E, to select Class B (Style B) move JW1 &am
10Zone Adder Module (Model ZA-42)Figure 6: ZA-42 Zone Adder ModuleClass A / B Selection: JW2 & JW3 are connected from 1 to 2 for initiating circu
11UDACT / DACT (Model UDACT-9100)P1: Cable to P8 on the main fi re alarm board.Jumper JW6 on the main fi re alarm module must be removed if a UDACT-9100
12Field WiringGeneral Field Wiring ConsiderationsBecause most of the Field Wiring on the PFC-5000’s is to the Main Boards on the swinging dead front,
13/Main Fire Alarm Module Terminal ConnectionsWire devices to terminals as shown in Figure 11 below. See Wiring Tables on page 20 for wiring instructi
14Figure 11B: Main Fire Alarm Module Terminal Connections (cont’d)When wiring devices, please keep in mind the following:All terminals are shown from
15Figure 12: Zone Adder Module (ZA-42) Terminal ConnectionsWire devices to terminals as shown below in Figure 12. See Wiring Tables on page 20 for wir
List of Figures and TablesFiguresFigure 1: PFC-5002 and PFC-5004 Enclosure Installation and Dimensions ...5Figure 2:
16Figure 13: Relay Module (ARM-4 or ARM-8) Terminal ConnectionsNote that only relays #1 to #4 are present on the ARM-4.NONCRELAY #2COMNONCRELAY #1COMN
17UDACT / DACT (UDACT-9100) Terminal ConnectionsThe following diagram shows the wiring connection for the UDACT-9100, refer to LT-888POT for more deta
18Polarity Reversal and City Tie Module (Model:PR-5100) Terminal ConnectionsSee Appendix C on page 37 for module specifi cations. Wire as shown in Figu
19Power Supply ConnectionsThe power supply is part of the main fi re alarm module and the chassis. The ratings are:Model Branch Circuit RatingsPFC-5002
20Wiring TablesTable 1: Wiring Table for Initiating CircuitsWire Gauge Maximum Wiring Run to Last Device (ELR)(AWG) ft. m22 2990 91020 4760 145018 756
21System CheckoutBefore Turning The Power On...1. To prevent sparking, do not connect the batteries. Connect the batteries after powering the system
22FIREDRILLSIGNALSILENCEAUXILIARYDISC.A.C. ONCOMMONALARMCOMMONSUPERVISORYCOMMONTROUBLEBATTERYTROUBLEGROUNDFA U LTREMOTETROUBLETESTDISC. 1ZONE 1ZONE 2
23Common Supervisory LED (PFC-5004 or PFC-5004E/PFC-5008 only)The amber Common Supervisory LED illuminates steadily when there is a supervisory alarm
24 ControlsSystem Reset SwitchThe System Reset momentary switch resets the fi re alarm control panel and all circuits:Resets all latching trouble condi
25OperationAll alarm inputs are treated in a similar manner. Alarm inputs include non-verifi ed or verifi ed alarms, and water-fl ow alarms. Activation o
Table of ContentsIntroduction ...
26Initiating (Detection) Circuit TypesCircuit Type DescriptionNon-Verifi ed AlarmThis is a “normal” type of alarm which may have pull stations, smoke d
27NAC (Signal) Circuits TypesCircuit Type DescriptionSilenceable Signal For audible devices such as bells and piezo mini-horns that may be silenced ei
28System Confi gurationMain Fire Alarm BoardConfi guration of the PFC-5000 Series is accomplished simply by DIP Switch Settings on the Main Fire Alarm B
29Table 3: Confi guration DIP Switch Functions on Main Fire Alarm BoardFunction DIP Switch Switch "Off" Switch "On"NAC Circuit #1Au
30When confi guring the PFC-5000 main board, keep in mind the following information:Only NAC circuit 2 may be confi gured for visual devices.• If initia
31Table 4: Confi guration DIP Switch Functions on ZA-42 ModuleFunction DIP Switch on ZA-42 ModuleSwitch "Off" Switch "On"NAC Circui
32Walk Test OperationA walk test allows an installer to verify the Initiating Circuit wiring in a system. To enter walk test, press and hold both the
33Appendix A: Compatible Devices(ULC) Canadian: Two-wire Smoke Detector Control Panel CompatibilityNote:Whether mixing different models of compatible
34(UL) United States: Two-Wire Smoke Detector Control Panel CompatibilityNote:Whether mixing different models of compatible smoke detectors or using t
35(UL) United States: 4-Wire Smoke Detector Control Panel CompatibilityMircomMIR-545U MIR-545TUSentrol - ESL541C449AT, 449C, 449CT, 449CRT, 449CST, 44
Appendix B: Remote Annunciators ...36Appen
36Appendix B: Remote AnnunciatorsThe RA8F Eight Zone Remote Annunciator mounts in an electrical box. It provides annunciation for the PFC-5004, PFC-50
37Appendix C: Module Specifi cations And FeaturesPFC-5002 Fire Alarm Control PanelGeneralTwo supervised Class B (Style B) or one Class A (Style D) Init
38ZA-42 Zone Adder ModuleMay be added to PFC-5004E.4 supervised Class B (Style B) or 2 Class A (Style D) initiating circuits; confi gurable. [Compatibi
39Appendix D: Power Supply & Battery CalculationsUse the form below to determine the required main chassis and secondary power supply (batteries).
40POTTER ELECTRIC SIGNAL COMPANY, LLCSt. Louis, MO (866) 956-1211 • (314) 595-6900 • FAX (314) 595-6999www.pottersignal.comWARRANTY INFORMATIONThe ess
1IntroductionAbout this ManualThis installation and operation manual provides information on installing and operating the PFC-5000 Microprocessor-Base
2Document ConventionsCircuits and ZonesThe term circuits refers to an actual electrical interface, initiating (detection), NAC (signal), or relay.The
3Model DescriptionPFC-5002 Small enclosure fi re alarm control panel with 2 Class B (Style B) or 1 Class A (Style D) Initiating Circuits, and 2 Power L
4Model DescriptionZA-42 Zone Adder Module for the PFC-5004E. Brings the total capacity to 8 Class B (Style B) or four Class A (Style D) Initiating Cir
5Mechanical Installation and DimensionsDOORBACKBOXWALL(SIDE VIEW)SURFACEDOOR83"3-BACKBOXDIA.WALL(SIDE VIEW)FLUSHBACKBOXDOOR-165"1343-"&